Permit: T06CM01647


Addresses:

10537 E OTTOMAN DR


Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T06CM01647

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2006 ROOF NAILING Approved IVRS - Inspection :*
12/15/2006 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/06/2006 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE PAPER ON ROOF AND TILE
2) CAN'T VERIFY IF TRUSSES ARE BROKEN FOIL INSTALLED UNDERNEATH OF TRUSSES
3) VERIFY P.A.'S
4) VERIFY 1ST & 2ND FLOOR STRAPS
5) MISSING WIND BRACE EAST SIDE 2ND FLOOR AND 1ST FLOOR WEST KITCHEN
6) INSTALL HEADER AT FIREPLACE
12/05/2006 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GABLE END TRUSS BLOCKING PER 2/D2 NOT MET
2) NEED COIL STRAP AT POST SHEARWALL 2ND FLOOR
3) NAIL SHEAR TRANSFER PER 1/D3
11/06/2006 ROOF NAILING Cancelled IVRS - RI canceled
11/06/2006 ROOF NAILING Partial Approval
11/02/2006 ROOF NAILING Partial Approval IVRS - Inspection :*
1) LOADED AND DRYED IN
2) AT ENTRY DAMAGED STUD NAIL 2 X 4 TO PORCH HEADER FRONT, GARAGE SHEAR
3) TIE REAR SHEAR TO TRUSS #3 24" ON CENTER A3.5
4) INTERSECTING WALL OSB TO OUTSIDE A-MODEL /SEE SHEAR PAGE 2ND FLOOR