Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01632
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FILL HOLE IN PANEL 2. OPEN NEUTRAL ON WASHER CIRCUIT WHEN GFI IS TRIPPED 3. EXHAUST FAN MUST BE ON FOR LAUNDRY LITE TO WORK AND FOR HALL OUTLET TO WORK. 4. RECEP NW CORNER 4R INOP. IS ONE TO THE RIGHT OF IT COVERED WITH SHEETROCK? 5. RAISE "T" ON PRIMARY CONDENSATE DRAIN 6. FRONT PORCH LIGHT INOP. 7. REMOVE GAS FLEX FROM BACK PORCH AND CAP VALVE OR LINE |