Inspection History Details
Permit: T06CM01631
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 06/29/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) CHECK ALL HANGER NAILS 2) 7/D2 CHECK NAILS IN ALL HANGERS, BLOCK BETWEEN TRUSSES AFTER NAILS APPROVED 3) MISSED P.A. REAR 4) PLUMB TRUSSES AT GIRDER 5) TRUSS REPAIR AT NOTCHED GABLES 6) SEE ITEMS ABOVE 7) 2-2 X 4 FROM GIRDER POST DOWN TO FLOOR |
|
| 06/19/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WRONG SIZE NAILS IN ALL P.A. STRAPS-REPLACE WITH 16D SINKERS 2) WRONG SIZE NAILS IN TRUSS HANGERS-REPLACE WITH 16D SINKERS 3) MISSED P.A. REAR WALL 4) PLUMB ROOF TRUSS 5) SHEAR TRANSFER NOT DONE 6) NO NOTCHING TOP CHORD/TRUSS REPAIR 7) MISSING PAGE D-6, D-7 & D-8 8) FOR ROOF ACCESS NAIL 2 X 4 TO ROOF AT 2ND FLOOR WINDOW 9) DID NOT WALK ROOF |