Inspection History Details
Permit: T06CM01629
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO DRY IN ROOF AND WALLS 2) BROKEN TRUSS REAR GABLE |
|
| 06/19/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* | |
| 06/14/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FRONT. COL. BOTTOM PLATES SPLIT 2. TRUSS DRAWINGS ON NOTES, RECOMMEND 2X6 STRONG BACKS. 3. P.A AT RETRO WALL 1ST & ENTRY 4. MISSING WIND BRACE NORTH WALL. 5. SHEAR WALLS NOT TRANSFERRED TO (DRAG TRUSS). 6. BELLY BAND NOT NAILED N/E CORNER 7. NEED CONNECTION REAR SHEAR BAND TOO SMALL 8. 2ND FLR PLATES NOT NAILED. 9. FREEZE BLKS NOT NAILED TO ROOF. 10. SHEAR WALL 2ND FLR. NORTH TO RUN TO OUTSIDE OF WALL. 11. BROKEN FLR TRUSS LAUNDRY. 12. NO NOTCH ON 24" FROM HEEL JOINTS (END TRUSS) 13. MISSED NAILING ROOF 14. BLK OSB TURNED WRONG WAY |