Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTEND SUN SHIELDS DOWN TO COVER ALL CANVAS 2) PERMANENTLY ID UNITS 3) CONDENSATE WATER LEAKING FROM EAST UNIT DRAIN CONNECTOR 4) PROVIDE TRAPS ON CONDENSATE DRAINS 5) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED TO FUSE ACCORDINGLY 6) CONDENSOR IS OVERFUSED 7) PROVIDE ISOLATORS UNDER CONDENSOR AS PER PLANS 8) PROVIDE CONDENSATE RECEIVER OR HAVE DELETED FROM PLANS 9) PROVIDE AIR BALANCE REPORT 10) PROVIDE PROPER LENGTH SENSING TUBES ON DUCT SMOKE DETECTORS |