Permit: T06CM01620

Parcel: 13312068G

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/10/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND SUN SHIELDS DOWN TO COVER ALL CANVAS
2) PERMANENTLY ID UNITS
3) CONDENSATE WATER LEAKING FROM EAST UNIT DRAIN CONNECTOR
4) PROVIDE TRAPS ON CONDENSATE DRAINS
5) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED TO FUSE ACCORDINGLY
6) CONDENSOR IS OVERFUSED
7) PROVIDE ISOLATORS UNDER CONDENSOR AS PER PLANS
8) PROVIDE CONDENSATE RECEIVER OR HAVE DELETED FROM PLANS
9) PROVIDE AIR BALANCE REPORT
10) PROVIDE PROPER LENGTH SENSING TUBES ON DUCT SMOKE DETECTORS