Permit: T06CM01620

Parcel: 13312068G

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) POLE BOND JUMPER TO BE SAME SIZE AS GROUNDING ELECTRODE CONDUCTOR
2) FINISH ITEMS #5, 7, 8 & 10 OF PREVIOUS INSPECTION
08/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
UNIT OCCUPIED WITHOUT FINAL INSPECTIONS -
NO OCCUPANCY ALLOWED
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS - 314.20
2. PANEL LABELING TO BE AS PER 408.4 - NO ABBREVIATIONS
3. LABEL TIME CLOCKS
4. BOND BUSHING NEEDED AT CONCENTRICS - 250.97
5. MISSING DEVICE & COVER OUTSIDE
6. LABEL ALL DISCONNECTS
7. BOND POLES PER 250.54 USE CORRECT SIZED WIRE NUTS PER LISTING
8. MAINTAIN WORKING CLEARANCES AT AC
9. FINISH SIGN CIRCUIT
10. INSTALL BREAKER NUMBER PANEL "HA"
11. PLEASE PROVIDE ACCESS TO HIGH BAY LIGHTING TO INSPECT