Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) POLE BOND JUMPER TO BE SAME SIZE AS GROUNDING ELECTRODE CONDUCTOR 2) FINISH ITEMS #5, 7, 8 & 10 OF PREVIOUS INSPECTION |
|
| 08/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT OCCUPIED WITHOUT FINAL INSPECTIONS - NO OCCUPANCY ALLOWED 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS - 314.20 2. PANEL LABELING TO BE AS PER 408.4 - NO ABBREVIATIONS 3. LABEL TIME CLOCKS 4. BOND BUSHING NEEDED AT CONCENTRICS - 250.97 5. MISSING DEVICE & COVER OUTSIDE 6. LABEL ALL DISCONNECTS 7. BOND POLES PER 250.54 USE CORRECT SIZED WIRE NUTS PER LISTING 8. MAINTAIN WORKING CLEARANCES AT AC 9. FINISH SIGN CIRCUIT 10. INSTALL BREAKER NUMBER PANEL "HA" 11. PLEASE PROVIDE ACCESS TO HIGH BAY LIGHTING TO INSPECT |