Permit: T06CM01620

Parcel: 13312068G

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/21/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
OK HARD LIDS
OK FRONT SOFFIT
06/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
STOP DRYWALL SOUTH WALLS

1. FINISH VDV CABELING USING LISTED PRODUCTS
06/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS EXCEPT AS NOTED
2) FINISH VDV CABELING
06/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO MORE THAN 360 DEGREE IN A CONDUIT RUN
2) SUPPORT VDV CABELING PER 725.6, 820.6 AND 800.6 PROTECT FROM SHAPR METAL EDGES ACCROSS STUDS
3) OK WEST WALL
05/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FILL UNUSED OPENINGS IN DISCONNECT & PANEL
2. TIGHTEN LOOSE FITTINGS
3. WHERE DOES #4 IN DISCONNECT GO TO?
4. MYERS HUB NOT LISTED FOR BONDING 250.92
5. PLEASE OPEN TRANSFORMER
6. MISSING DEAD FRONT COVER
7. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND
BARS 250.8
8. TIGHTEN LOOSE CONDUCTOR TERMINATIONS
9. NEUTRAL BLOCK COMING LOOSE
10. CORDS IN DETERRIORATED CONDITION -- NEED REPLACEMENT
11. PLEASE ADD TEMP POWER FOR CONSTRUCTION TO PERMIT