Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS OK HARD LIDS OK FRONT SOFFIT |
|
| 06/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* STOP DRYWALL SOUTH WALLS 1. FINISH VDV CABELING USING LISTED PRODUCTS |
|
| 06/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS EXCEPT AS NOTED 2) FINISH VDV CABELING |
|
| 06/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREE IN A CONDUIT RUN 2) SUPPORT VDV CABELING PER 725.6, 820.6 AND 800.6 PROTECT FROM SHAPR METAL EDGES ACCROSS STUDS 3) OK WEST WALL |
|
| 05/02/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FILL UNUSED OPENINGS IN DISCONNECT & PANEL 2. TIGHTEN LOOSE FITTINGS 3. WHERE DOES #4 IN DISCONNECT GO TO? 4. MYERS HUB NOT LISTED FOR BONDING 250.92 5. PLEASE OPEN TRANSFORMER 6. MISSING DEAD FRONT COVER 7. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND BARS 250.8 8. TIGHTEN LOOSE CONDUCTOR TERMINATIONS 9. NEUTRAL BLOCK COMING LOOSE 10. CORDS IN DETERRIORATED CONDITION -- NEED REPLACEMENT 11. PLEASE ADD TEMP POWER FOR CONSTRUCTION TO PERMIT |