Permit: T06CM01602

Parcel: 108203400


Addresses:

4179 N FORTUNE LP

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/31/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
01/25/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER HEATER VENT TOUCHING WOOD, IS CROOKED & EXTEND DOWN BELOW CEILING IN ENCLOSURE.
EXTENSION THRU ROOF NOT CONNECTED TO ELBOW.
12/15/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER HEATER VENT TOO CLOSE TO FIREBLOCK PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLE. REMOVE SPRAY FOAM OR PROVE THAT FOAM IS NON-COMBUSTIBLE
JOINTS STILL NOT SEALED ON KITCHEN VENT.
HOW ARE YOU GOING TO CONNECT EXHAUST HOOD TO DUCT AFTER SHEETROCK IS INSTALLED? SUPERINTENDENT & MECH. CONTRACTOR MUST BE HERE FOR NEXT INSPECTION.
12/06/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE FOAM & PROVIDE AT LEAST 60 DEG. SLOPE ON WATER HEATER VENT.
2. EXTEND UP THRU ROOF.
3. REGISTER BOXES 2ND FLOOR STILL NOT INSULATED.
4. NO CORRECTIONS HAVE BEEN MADE
5. PROVIDE A FILTER RACK FOR OUTSIDE AIR INTAKE
6. SEAL ALL JOINTS ON KITCHEN VENT.
7. PROVIDE A CONNECTOR FOR THE RANGE HOOD.

GO BACK TO LOT 41 & SEAL 1 JOINT ON KITCHEN EXHAUST.
10/12/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 2ND FLR. 20X6 TAPERED SUPPLY REG. TAP, INSULATE REAR SIDE OF TAP.
2. REMOVE FOAM AT WATER HTR. VENT THIMBLE THRU WALL LOCATION B-1 WATER HTR. VENT NEEDS TO BE ADJUSTED.