Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/11/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU MUST CONFORM TO APPEAL FOR PLUMBING COMMON WALL |
|
| 12/15/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* SEE NOTES DATED 12/6/06 |
|
| 12/06/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* I NEED TO SEE APPROVED APPEAL FORM AND FIRESTOP AT 3" PENETRATION |
|
| 09/25/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOU MAY NOT HAVE ANY PLUMBING OR DUCTS IN COMMON 2 HOUR WALLS (IRC 317.2) YOU MUST REVISE YOUR PLAN. REMOVE PLUMBING FROM COMMON WALL OR REDESIGN SO THAT INSTEAD OF A 2HR COMMON WALL YOU HAVE 2- 1 HOUR WALLS. 2. REPAIR FOR DWV TO COME OUT OF COMMON WALL AT FLOOR LEVEL WILL REQUIRE APPEAL TO BLD. OFFICIAL. |
|
| 09/21/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |