Permit: T06CM01601

Parcel: 11005318D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/05/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CONNECTIONS AT HYDRO SAN ARE OK
2) BACKFLOW CERTS RECEIVED
3) 1/2" PIPING AND RPS INSTALLED OUTSIDE ARE SUBJECT TO FREEZE DAMAGE-INSULATE OR PROVIDE PROTECTIVE ENCLOSURE
01/05/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. PIPING AT COLONIC OK TO COVER.
2. PROVIDE BACKFLOW CERTS.
3. INSULATE EXTERIOR PIPING.
12/29/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) ALL AREAS ARE COMPLETE EXCEPT AT HYDRUSAN (COLONIC)
2) I SEE NO HAZARDS TAHT WOULD PREVENT A TCO
3) HYDROSAN SHALL NOT BE USED UNTIL INSPECTED, AND BACKFLOW PROTECTION ON HOT AND COLD WATER NEEDED UNLESS A LISTING IS PROVIDED FOR BACKFLOW CONDITIONS
2) I SEE NO HAZARDS THAT WOULD PREVENT A TCO
3) HYDROSAN
12/26/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
COMPLETE CLEANOUTS AT URINAL,
WATER HEATER AND REAR SEWER
COMPLETE ICE MAKER DRAIN CONNECTIONS,
PIPING TO BE SECURE AND HAVE 1" AIR GAP
INSTALL HYDROSAN AIR GAP OR BACKFLOW DEVICE NEEDED
BACKFLOW CERTS RECEIVED FOR IRR. AND ICE MAKER OTHER CORRECTIONS OK
12/19/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HB AT METER, WATER LINE ON ROOF, HB VACUUM BREAKERS.
2. FUTURE CONNECTION AT SW CORNER? BACKFLOW PROTECTION FOR IRRIGATION.
3. ONE P-TRAP PER TRAP ARM.
4. TRAFFIC RATED SEWER CLEANOUT COVERS IN PARKING AREA, BRASS COVERS AT REAR.
5. VAC BREAKER AT HAND HELD SHOWER.
6. INTERNAL BACKFLOW CERTS
7. OPEN FRONT TOILET SEATS
8. PROTECT PVC VENT TERMINATIONS.