Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/07/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PLAN SPECS ABS PROVIDE DOCUMENTATION FOR PVC DWV - PROVIDE DETAIL AND PLAN FOR WATER FOUNTAIN TO BE INSTALLED. - PROVIDE METHOD OF COUPLING WITH ENERGY CONSERVATION CODES FOR HW. - HAVE DECORATIVE WATER FEATURE ADDED TO PLAN, PROVIDE SPEC AND METHOD OF BACKFLOW PROTECTION. - GAS PRESSURE GAUGE IS TO BE 1/10TH PSI INCREMENTATION - SUPPORT CSST AT BRANCH CONNECTION TO MAIN -- PROVIDE MANUFACTURERS SPECS. - OK TO COVER ALL BUT AT DFS |
|
| 08/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - CHANGES ON DWV OR PROVIDE SAFETY PLATES WHERE PIPES ARE WITHIN 1 1/4" OF STUD. - NO PROBLEM W/COVERING ONE SIDE OF WALL. |
|
| 08/21/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* - POST ADDRESS - HORIZONTAL CHANGES OF DIRECTION ON WASTE PIPING TO BE MADE W/WYE PATTERN FITTINGS OR SWEEPS OF EQUIVALENT RADIUS. - FERNED COUPLINGS NOT ALLOWED INSIDE BUILDING. - USE APPROVED HANGERS ON PVC. - CLEAN OUT EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS. - SAFETY PLATES NEEDED. - PROVIDE A GAS PIPING PLAN W/MATERIAL TYPE AND SIZE. - PROVIDE A WATER PIPING PLAN WITH ACCURATE FIXTURE COUNT AND PIPE SIZING. INCLUDE WATER FEATURES AND BACKFLOW PROTECTION. - NOTE: EXISTING TOILET ROOMS HAVE BEEN REPIPED - PROVIDE HAMMER ARRESTORS AT QUICK CLOSING VALVES. - IT DOES NOT APPEAR THAT YOUR EXISTING RESTROOM WILL MEET ADA REQUIREMENTS. |