Permit: T06CM01601

Parcel: 11005318D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/11/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/07/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- PLAN SPECS ABS PROVIDE DOCUMENTATION FOR PVC DWV
- PROVIDE DETAIL AND PLAN FOR WATER FOUNTAIN TO BE INSTALLED.
- PROVIDE METHOD OF COUPLING WITH ENERGY CONSERVATION CODES FOR HW.
- HAVE DECORATIVE WATER FEATURE ADDED TO PLAN, PROVIDE SPEC AND METHOD OF BACKFLOW PROTECTION.
- GAS PRESSURE GAUGE IS TO BE 1/10TH PSI INCREMENTATION
- SUPPORT CSST AT BRANCH CONNECTION TO MAIN -- PROVIDE MANUFACTURERS SPECS.
- OK TO COVER ALL BUT AT DFS
08/28/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- CHANGES ON DWV OR PROVIDE SAFETY PLATES WHERE PIPES ARE WITHIN 1 1/4" OF STUD.
- NO PROBLEM W/COVERING ONE SIDE OF WALL.
08/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- POST ADDRESS
- HORIZONTAL CHANGES OF DIRECTION ON WASTE PIPING TO BE MADE W/WYE PATTERN FITTINGS OR SWEEPS OF EQUIVALENT RADIUS.
- FERNED COUPLINGS NOT ALLOWED INSIDE BUILDING.
- USE APPROVED HANGERS ON PVC.
- CLEAN OUT EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS.
- SAFETY PLATES NEEDED.
- PROVIDE A GAS PIPING PLAN W/MATERIAL TYPE AND SIZE.
- PROVIDE A WATER PIPING PLAN WITH ACCURATE FIXTURE COUNT AND PIPE SIZING. INCLUDE WATER FEATURES AND BACKFLOW PROTECTION.
- NOTE: EXISTING TOILET ROOMS HAVE BEEN REPIPED
- PROVIDE HAMMER ARRESTORS AT QUICK CLOSING VALVES.
- IT DOES NOT APPEAR THAT YOUR EXISTING RESTROOM WILL MEET ADA REQUIREMENTS.