Permit: T06CM01601

Parcel: 11005318D

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
02/06/2007 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
12/15/2006 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
OK PARKING LOT CONDUITS
12/14/2006 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
12/11/2006 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT FIXTURE WITH SUPPORT WIRE
2. SUPPORT VDV CABELING AS PER CODES 725.6, 760.6, 800.6
3. SUPPORT M/C CABLES 6' INTERVALS AND OFF OF GRID.
4. CONDUITS TO BE 24" UNDER PARKING OR DRIVE 300.5

* BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR TO BE FLUSH IN COMBUSTIBLES MAY NEED APPROVED EXTENDER RINGS - 314.20