Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/26/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 12/22/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORTS FOR LIGHTING & VDV TO BE PER 300.11 2. MEDICAL LIGHTS TO BE AS PER 517.13 |
|
| 12/21/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/11/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/14/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PROGRESS OK OK CONTINUE WORK ON CEILING, FINISH SEISMIC SUPPORTS TIE IN BRANCH CIRCUITS. ONCE SERVICE WORK FINISHED CALL IN FOR POWER CLEARANCE OK ON PROGRESS INSPECTION. |