Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/21/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. BONDING TO BE AS PER 250.102 & 250.66 2. INSTALL GROUNDING ELECTRODE SYSTEM AS DISCUSSED WITH GROUNDING ELECTRODE TAPS. 3. INSTALL LISTED BRACE KIT FOR RISERS |
|
| 09/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | OK FLOOR BOXES OK WALLS |
|
| 09/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ROCK EXCEPT WHERE VDV CABLEING IS 1. SUPPORT VDV CABLEING #4 OF A PREVIOUS INSPECTION. |
|
| 08/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CHELATION ROOM TO BE PER 517.13 2. FILL UNUSED OPENINGS OK TO ONE SIDE. |
|
| 08/16/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. FLOUR BOXES TO MEET REQUIRMENTS OF 517.13 (A) & (B) 2. PROVIDE BACK BRACING FOR BOXES WITH M/C CABLE AND METAL STUDS. 3. PROTECT M/C IN CHANNEL 4. SUPPORT VDV CABLEING IN WALLS. |