Permit: T06CM01601

Parcel: 11005318D

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/21/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. BONDING TO BE AS PER 250.102 & 250.66
2. INSTALL GROUNDING ELECTRODE SYSTEM AS DISCUSSED WITH GROUNDING ELECTRODE TAPS.
3. INSTALL LISTED BRACE KIT FOR RISERS
09/12/2006 ELECTRIC - INTERMEDIATE Partial Approval OK FLOOR BOXES
OK WALLS
09/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ROCK EXCEPT WHERE VDV CABLEING IS
1. SUPPORT VDV CABLEING #4 OF A PREVIOUS INSPECTION.
08/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CHELATION ROOM TO BE PER 517.13
2. FILL UNUSED OPENINGS

OK TO ONE SIDE.
08/16/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. FLOUR BOXES TO MEET REQUIRMENTS OF 517.13 (A) & (B)
2. PROVIDE BACK BRACING FOR BOXES WITH M/C CABLE AND METAL STUDS.
3. PROTECT M/C IN CHANNEL
4. SUPPORT VDV CABLEING IN WALLS.