Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE REVISE PLANS TO REFLECT WORK INSTALLED OR INSTALL AS PER PLANS. 2. WE HAVE MULTIPLE TERMINATIONS AT LUGS. 3. NEED ANTI-OXIDE COMPOUND AT TERMINATIONS 4. WE HAVE PARALLEL PATHS OF GROUND. |
|
| 08/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT AND ANSWER QUESTIONS. SERVICE IS ENERGIZED WITHOUT CLEARANCE. 2. VERIFY PROTECTION OF CONDUCTORS PER TAP RULES 240.21 3. LABEL ELECTRICAL EQUIPMENT. |