Permit: T06CM01595

Parcel: 105102410

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM01595

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
07/13/2006 PLUMBING - ROUGH, SOIL Partial Approval PLUMBER HAS PROBLEMS WITH DEPTH AND WITH THE PLAN
HE HAS INSTALLED WHAT LOOKS LIKE A WORKABLE SYSTEM NOW WE NEED REDLINES TO MATCH INSTALLATION.
07/05/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PLAN APPROVED IN ERROR.
2. GREASE WASTE NOT INSTALLED PER PLAN
- VENT DOWNSTREAM OF TRAP.
- FLOW CONTROL AT EACH FIXTURE.
3. USE OF COMBINATION WASTE AND VENT IS NOT WARRANTED NOR IS IT ACCEPTABLE IN THIS APPLICATION.
4. IF CONTRACTOR RECONFIGURES HIS BUILDING DRAIN AND VENTS INTO THE 6" PARTITION HIS PLUMBING WILL WORK ALSO CHANGES REQUIRE REVISION.