Permit: T06CM01595

Parcel: 105102410

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01595

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK ELECTRICAL FINAL

RICHARD 310-505-0164
08/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY'S CORRECTLY - NEC 408.4
2. REAR EMERGENCY LIGHT NOT WORKING
3. BOND ALARM PANEL PER INSTRUCTIONS - NEC 110.3
4. PROVIDE 2 POLE BREAKERS AS REQUIRED ON RECEPTACLES - NEC 210.7(C)
5. SEE RICHARD FOR ALL ROOF TOP CORRECTIONS, WORKING GFI, DISCONNECT PROBLEMS AND IDENTIFY ALL EQUIPMENT, #8 FUSE @ 45