Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01595
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK ELECTRICAL FINAL RICHARD 310-505-0164 |
|
08/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY PANEL DIRECTORY'S CORRECTLY - NEC 408.4 2. REAR EMERGENCY LIGHT NOT WORKING 3. BOND ALARM PANEL PER INSTRUCTIONS - NEC 110.3 4. PROVIDE 2 POLE BREAKERS AS REQUIRED ON RECEPTACLES - NEC 210.7(C) 5. SEE RICHARD FOR ALL ROOF TOP CORRECTIONS, WORKING GFI, DISCONNECT PROBLEMS AND IDENTIFY ALL EQUIPMENT, #8 FUSE @ 45 |