Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM01595
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/14/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN CEILING AFTER CORRECTIONS COMPLETE -- WILL CHECK ON FINAL. |
|
08/11/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE EQUIPMENT GROUND TO GROUND ALL METAL BOXES NEC 250.4 2. SUPPORT ALL FIXTURES INCLUDING TRACK LIGHTING AND RECEPTACLES WITH WIRES TO STRUCTURE NEC 410.104/NEC 300.11 3. CORD AND PLUG CONNECTED EQUIPMENT NOT ALLOWED ABOVE SUSPENDED CEILING NEC 400.8 (5) 4. CAN LIGHTING J-BOXES ARE OVERFILLED IN SOME LOCATIONS -- NEC 110.3 5. SUPPORT ALL MC OFF GRID AND WITHIN 12" OF TERMINATION AND 6' INTERVALS NEC 330 6. SUPPORT LOW VOLTAGE WIRING OFF GRID |