Permit: T06CM01595

Parcel: 105102410

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/28/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/14/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN CEILING AFTER CORRECTIONS COMPLETE -- WILL CHECK ON FINAL.
08/11/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE EQUIPMENT GROUND TO GROUND ALL METAL BOXES NEC 250.4
2. SUPPORT ALL FIXTURES INCLUDING TRACK LIGHTING AND RECEPTACLES WITH WIRES TO STRUCTURE
NEC 410.104/NEC 300.11
3. CORD AND PLUG CONNECTED EQUIPMENT NOT ALLOWED ABOVE SUSPENDED CEILING NEC 400.8 (5)
4. CAN LIGHTING J-BOXES ARE OVERFILLED IN SOME LOCATIONS -- NEC 110.3
5. SUPPORT ALL MC OFF GRID AND WITHIN 12" OF TERMINATION AND 6' INTERVALS NEC 330
6. SUPPORT LOW VOLTAGE WIRING OFF GRID