Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK U.G CONDUITS FOR COOLING TOWER PUMPS - OK 1 1/2" TO REFEED GUTTER #1, ALSO MCC TO AH #1, FROM AH #2 TO AH #4 - 2" CONDUIT. - 75 KVA INSTALLED PER PLAN BUT NOT CODE COMPLIANT PER 450.13 NEC GROUND PER 250.30 250.104.4 |
|
| 04/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ROOM 110 - SERVER RM OK TO COVER WALLS. 2. ROOM 123 - B-BLAST OK TO COVER WALLS. |
|
| 04/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNLISTED EQUIPMENT MUST MEET REQUIREMENTS OR 2002 NEC 110-3, OR IF ONE OF A KIND - REVIEW OF EQUIPMENT BY AN EE WITH STAMP IN AZ PROVIDE REPORT OF EE'S REVIEW OF EQUIPMENT INCLUDING DESCRIPTION & PROCESS OF EVALUATION. |