Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/06/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK U.G CONDUITS FOR COOLING TOWER PUMPS
- OK 1 1/2" TO REFEED GUTTER #1, ALSO MCC TO AH #1, FROM AH #2 TO AH #4 - 2" CONDUIT.
- 75 KVA INSTALLED PER PLAN BUT NOT CODE COMPLIANT PER 450.13 NEC GROUND PER 250.30 250.104.4
04/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ROOM 110 - SERVER RM OK TO COVER WALLS.
2. ROOM 123 - B-BLAST OK TO COVER WALLS.
04/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNLISTED EQUIPMENT MUST MEET REQUIREMENTS OR 2002 NEC 110-3, OR IF ONE OF A KIND - REVIEW OF EQUIPMENT BY AN EE WITH STAMP IN AZ PROVIDE REPORT OF EE'S REVIEW OF EQUIPMENT INCLUDING DESCRIPTION & PROCESS OF EVALUATION.