Permit: T06CM01584

Parcel: 133390370


Addresses:

9953 E CALDERA PL


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM01584

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) ROOF NAILING DOES NOT REQUIRE ADDITIONAL BLOCKS AT EDGE. JUST NAIL SHEATHING INTO 2 X 4 BIRD BOARDS
05/16/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NUMBERS 2, 3 AND 8 NOT DONE
05/12/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL OFF BIRD BOARDS PER 2 ON SD3
2) ADD SHEAR UNDER WINDOW BEDROOM AND COMPLETE NAILING SHEARWALL IN BEDROOM 4
3) COMPLETE NAILING SHEAR TOP OF WALL BEDROOM 3 AND SHEAR MASTER BEDROOM
4) ADD STUDS 3 PT BEARING TRUSS A28. REMOVE SHIMS WHERE NONE BEARING
5) ADD STUD AND SHIM A-17 AT MID POINT BEARING
6) WALKED WHOLE ROOF-OK EXCEPT PERIMETER
7) IF POSSIBLE, SUPPLY TRUSS DRAWINGS FOR EACH ELEVATION INSTEAD OF ONE PACKAGE FOR ALL ELEVATIONS
8) NAIL PROTECT PIPES AND CONDUIT AT EXTERIOR OF BOTTOM PLATES