Permit: T06CM01565

Parcel: 14117007F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01565

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SECURE CABLES AT PANEL 12" FROM PANEL & EVERY 6' AFTER.
2. CANNOT USE SHEETMETAL SCREW FOR GROUNDING
GROUND METAL BOX PER NEC 250
3. CHECK STRAPPING OF MC CABLES WITHIN 12" OF CONNECTION POINTS & EVERY 6' AFTER
4. CHECK EXITS FOR PROPER OPERATION
5. CHECK EM LIGHTS FOR PROPER OPERATION
6. CHECK ALL BOXES GROUNDED PER NEC 250
7. OVERFILL ON 4" SQUARE BOX EAST HALL
8. EGRESS LIGHTING NEEDS TO BE WIRED
9. INSTALL PANEL DIRECTORY
10. CONNECT GROUNDING ELECTRODE CONDUCTOR TO PANEL GROUND BAR
11. BOND BUILDING STEEL
12. CONNECT GROUND AT SWAMP COOLER OUTLET BOXES
13. SJ CORD FOR SWAMP COOLERS MARKED FOR INDOOR USE ONLY.