Permit: T06CM01563

Parcel: 14117007F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01563

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. GROUND ALL METAL BOXES PER NEC 250
2. CANNOT FEED THROUGH A/C DISCONNECT TO 2ND DISCONNECT PER NEC 312.8
3. NEED PROPER WORKING CLEARANCE AT A/C DISCONNECT PER 110.26
4. SEAL OPEN KNOCKOUT AT A/C DISCONNECT
5. BOND BUILDING STEEL TO PANEL PER NEC 250
6. INSTALL FILLER PLATES IN PANEL DEAD FRONT
7. EXIT & EM LIGHTS NOT OPERATING PROPERLY.
8. INSTALL COVER ON RECEPT EAST END OF BUILDING.