Permit: T06CM01562

Parcel: 14117007F

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T06CM01562

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
1) WILL LOOK FOR CORRECT SCREWS ON PANEL COVER 4-B
03/12/2007 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORRECT ADDRESS
2. PROVIDE LETTER ON CHANGE FROM COPPER TO DRUM AT SERVICE.
3. PROVIDE MAIN BONDING SCREW AT DISCONNECT
4. USE CORRECT WIRING METHOD AT METER BOND BUSHING
5. FUSES CALLED OUT FOR ARE LPN RK, FULL BLADE CONTACT
6. CORRECTLY CLAMP LOOSE BREAKER IN 400A PNL
7. FINISH J-BOX - GUTTER ABOVE PNL, INCLUDING GROUNDING TO BUSHING.
8. PNL 4-B BUSHING REG ON FEE, TAPE GROUND, 70 AMP AC NEED #4