Permit: T06CM01557

Parcel: 11620122A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/05/2007 BUILDING - FINAL Approved IVRS - Inspection :*
06/22/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECEPTACLES NOT PERMITTED UNDER BAR TOP E3801.4.5
2) RECEPTACLE FOR REFRIDGERATOR THAT IS OVER COUNTER SPACE NEEDS TO BE A SINGLE NOT A DUPLEX E3802.6
3) ? DUCT NOT PERMITTED FOR RANGE HOOD M1502.2
4) PENINSULAR RECEPTACLE REQUIRED WITHIN 12" OF COUNTER TOP E3801.4.3
5) VACCUM BREAKER NEEDED ON COURT YARD HOSE BIB
6) REPLACE BROKEN FIXTURE PLATE ON CEILING OF M. BEDROOM
7) VERIFY OUTDOOR LIGHTING COMPLIANCE
8) WEATHER PROOF A/C DISCONNECT
9) SECURE A/C DISCONNECT
10) BLOCK CONDENSATE DRAINS 4' ON CENTER
11) MARK HEAT STRIP LABEL