Permit: T06CM01543

Parcel: 140261000

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM01543

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/03/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE CORRECTIONS FROM THE PREVIOUS INSPECTION HAVE NOT BEEN MADE.
05/01/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UPC 314.3 -- "PIPING IN GROUND SHALL BE LAID ON A FIRM BED FOR ITS ENTIRE LENGTH"
PROVIDE SHADING OF PIPING WITH CLEAN COMPACTABLE FILL THAT DOES NOT CONTAIN ROCKS OR CHUNKS LARGER THAN 3/4".
UPC 708 -- HORIZONTAL DRAINAGE PIPING SHALL BE RUN IN PRACTICAL ALIGNMENT AND A UNIFORM SLOPE OF NOT LESS THAN 2%".
SUPPORT BRANCH AT WC.
UPC SEC 314.3 -- ALSO APPLIES TO YARD WATER PIPING.
TUBING SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS WHICH REQUIRE BEDDING, SHADING AND HAUNCHING AND SHALL COMPLY WITH UPC SECTIONS 310.3 --- 316.1.2, 316.1.2.3, 316.1.2.9 AND 609.4
REAM ALL TUBING!
PROVIDE A PRESSURE TEST AND SHADE WITH CLEAN FILL TO 6" ABOVE PEX TUBING -- LEAVE JOINTS EXPOSED FOR INSPECTION.