Permit: T06CM01542

Parcel: 140263800

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01542

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2006 FRAMING Approved IVRS - Inspection :*
10/16/2006 FRAMING Partial Approval IVRS - Inspection :*
1) COMPLY WITH PREVIOUS NUMBERS 5, 6 & 7
2) OK TO INSULATE
3) EXPOSE REPAIRED AREAS
10/12/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
10/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTINOUS LOAD TRANSFER REQUIRED FROM 2ND FLOOR GIRDERS
2) EXTEND SHEAR TO TOP PLATE 2ND FLOOR
3) 1/4" PER FOOT SLOPE REQUIRED AT WASTE AT GARAGE
4) 10 POUND MINIMUM REQUIRED ON GAS LINE TEST
5) 1" CLEARANCE REQUIRED FROM COMBUSTIBLE TO B-VENTS
6) FIRE BLOCK 2ND FLOOR POP OUT SOUTH SIDE
7) STRAP BEAM TO POST 1ST FLOOR BETWEEN LIVING ROOM AND DINING
8) 2-2 X 8 HEADER REQUIRED OVER KITCHEN WINDOW
07/23/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT COMPLETE ENOUGH TO INSPECT