Permit: T06CM01526

Parcel: 140550850

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/23/2006 FRAMING Approved IVRS - Inspection :*
1) ITEM 03050 NOT REQUIRED PER J. RIVA
05/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECOND FLOOR LATH NOT COMPLETE
2) SW 8 REQUIRED AT 24" ON CENTER
3) BLOCK DUCT BOOTS 3 SIDES
4) SHORT RADIUS 90'S CANNOT BE ON BOTTOM CLOSET ? OR STACK
05/18/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
NOT READY PER SUPER
05/17/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY SUPER