Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM01519
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2006 | FRAMING | Approved | IVRS - Inspection :* | |
09/01/2006 | FRAMING | Partial Approval | IVRS - Inspection :* COMPLETE #3 |
|
08/30/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) TIGHTEN RED HEADS 2) INSTALL CHASE AT 3' ABS 3) COMPLETE BLOCKING OF TOP OF A/C CHASE 4) REPAIR PAPER AT SGD 5) TWO WINDOWS S.E. CORNER NOT INSTALLED 6) REMOVE SCREW AND RECEPTACLE UNUSED 3" ABS IN KITCHEN 7) NEED 12" PEX TO LIGHTS IN KITCHEN 8) PROPERLY SUPPORT ABS UNDER STAIRS 9) NO SUPPLY PRESSURE TEST 10) RELIEF AIR IN GARAGE NOT INSTALLED 11) CHANGE SLOPE OF H20 B-VENT 12) LOWER MECHANICAL IN POWDER ROOM 13) MAKE UP AIR WITHIN 10' OF SEWER VENT |