Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM01513
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2009 | FRAMING | Approved | IVRS - Inspection :* PER AS-BUILTS APPROVED |
|
12/04/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER ABE |
|
07/02/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) UNTIL ITEM #2 COMPLETED FROM PRIOR INSPECTION |
|
06/25/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO COMPLETE HOME RUNS TO SERVICE PANELS 2) NEED FIRE SEAL ALL OPENINGS INTO CEILING AT 10' |
|
06/20/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO FIRE SEAL ALL CHASES 2) MISSING FIRE BLOCK IN CEILING LINE 3) NEED PROTECTION PLATE THROUGHOUT 4) NEED TO MAKE UP ALL GROUNDS IN RECEPTACLES AND SWITCH BOXES 5) NEED TO SEALL ALL PENETRATIONS IN FOAM FOR STUCCO 6) FRAME ALL OPENING FOR A/C UNIT (WINDOW) 7) NEED TO SEAL ALL CONDUCTOR WIRE, TO BE COVERED WITH STUCCO IN GREAT ROOM |