Permit: T06CM01512

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01512

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE TRANSFORMER TO FLOOR.
2. NEED BUSHINGS FOR #4 AND LARGER CONDUCTOR.
3. NEED 30" WIDE CLEARANCE IN FRONT OF DISCONNECT.
4. STRAP SECONDARY FLEX
5. FIX PANEL DIRECTORY SO IT FITS AND IS VISIBLE COMPLETELY