Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE TRANSFORMER TO FLOOR. 2. NEED BUSHINGS FOR #4 AND LARGER CONDUCTOR. 3. NEED 30" WIDE CLEARANCE IN FRONT OF DISCONNECT. 4. STRAP SECONDARY FLEX 5. FIX PANEL DIRECTORY SO IT FITS AND IS VISIBLE COMPLETELY |