Permit: T06CM01510

Parcel: 11505161B


Addresses:

2222 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01510

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. @ ALARM PANEL CLEAN UP WIRING, USE CONNECTORS
FOR CONDUCTORS ENTERING PANEL, PROVIDE EARTH GROUND - NEC 110.31, 800.6
2. HAVE OVERFILLED BOXES - NEC 314.16
3. HAVE UNGROUNDED BOXES - NEC 314.4, 250
4. EMERGENCY LIGHTING TO BE ON CKT FOR LIGHTING IN THAT AREA AND FIXTURE AT EXIT NOT CORRECT - NEC 700.12E
5. PROPERLY IDENTIFY NEUTRALS -- NEC 200.6
6. HARDWIRE CONDENSOR AND PROVIDE DISCONNECT -
NEC 400.109, NEC 400.8