Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01510
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. @ ALARM PANEL CLEAN UP WIRING, USE CONNECTORS FOR CONDUCTORS ENTERING PANEL, PROVIDE EARTH GROUND - NEC 110.31, 800.6 2. HAVE OVERFILLED BOXES - NEC 314.16 3. HAVE UNGROUNDED BOXES - NEC 314.4, 250 4. EMERGENCY LIGHTING TO BE ON CKT FOR LIGHTING IN THAT AREA AND FIXTURE AT EXIT NOT CORRECT - NEC 700.12E 5. PROPERLY IDENTIFY NEUTRALS -- NEC 200.6 6. HARDWIRE CONDENSOR AND PROVIDE DISCONNECT - NEC 400.109, NEC 400.8 |