Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* PROVIDE MIN. 1/8" PER FT SLOPE ON CONDENSATE DRAIN TERMINATE WITHIN 6" OF THE GROUND PROVIDE A FRESH AIR INTAKE EXTEND RAIN SHIELD OVER CANVAS OK FOR CEILING TILES |
|
| 06/22/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE APPROVED PLANS WHERE IS CONDENSATE DRAIN? R 4.2 FLEX DUCT NOT PER IECC CODE MUST BE MIN. R5 |
|
| 05/18/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EX. FAN HOUSING SUPPLY OK OK TO COVER |