Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2007 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 07/06/2007 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE A LETTER FROM ELECTRICAL CONTRACTOR STATING ALL TORQUE ON TERMINATIONS FOR CONDUCTORS AND SWITCH GEAR ARE AS PER MANUFACTURES REQUIREMENTS. 2. SERVICE MUST BE ADDRESSED 3. MUST USE FULL SURFACE CONTACT OF LUG AT GROUND ROD CLAMPS. |