Permit: T06CM01487

Parcel: 132130570


Addresses:

1051 E BENSON HY

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/30/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/29/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT MC WITHIN 12" OF TERMINATION &
AT 6' INTERVALS PER NEC
2. INSTALL 2 SEISMIC WIRES FOR EACH LAY IN GRID FIXTURE AND SCREW OR CLIP TO GRID.
05/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & HARD LIDS #1
OK WATER BOND, BLD. STEEL
05/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED LETTERS FOR GROUNDING & MC USE
05/07/2007 ELECTRIC - INTERMEDIATE Partial Approval OK CONTINUATION OF 3" SECONDARYS TO X-FORMER PAD
SUBJECT TO APPROVED 1 LINE DIA,
BE ADVISED THAT WARNING RIBBON REQUIRED 12" ABOVE CONDUITS. PER 300 NEC COULD NOT LOCATE ELECTRICIAN.
05/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OFFICE WALLS, SUBJECT TO APPROVAL FOR USE OF
MC CABLE.
PLANS MUST INCLUDE SERVICE INFO
OK U.G 3" SECONDARYS 20' NORTH OF SES
OK 2" PANEL FEEDERS FROM SES TO BLD#3