Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT MC WITHIN 12" OF TERMINATION & AT 6' INTERVALS PER NEC 2. INSTALL 2 SEISMIC WIRES FOR EACH LAY IN GRID FIXTURE AND SCREW OR CLIP TO GRID. |
|
| 05/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS #1 OK WATER BOND, BLD. STEEL |
|
| 05/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED LETTERS FOR GROUNDING & MC USE |
|
| 05/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | OK CONTINUATION OF 3" SECONDARYS TO X-FORMER PAD SUBJECT TO APPROVED 1 LINE DIA, BE ADVISED THAT WARNING RIBBON REQUIRED 12" ABOVE CONDUITS. PER 300 NEC COULD NOT LOCATE ELECTRICIAN. |
|
| 05/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OFFICE WALLS, SUBJECT TO APPROVAL FOR USE OF MC CABLE. PLANS MUST INCLUDE SERVICE INFO OK U.G 3" SECONDARYS 20' NORTH OF SES OK 2" PANEL FEEDERS FROM SES TO BLD#3 |