Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WIRE AND IDENTIFY BRANCH CKT'S AS SHOWN ON PLANS. 2. GROUND CHILLER DISCONNECT ENCLOSURE. 3. IDENIFY DISCONNECT. 4. MAX 25 AMP. FUSE FOR CHILLER. 5. NEED ROOFTOP SERVICE OUTLET WITHIN 25' OF CHILLER. |
|
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH WIRING BEFORE INSPECTION, PROVIDE ACCESS TO NEW CEILING WIRING. |