Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM01477

Parcel: 10321029W

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WIRE AND IDENTIFY BRANCH CKT'S AS SHOWN ON PLANS.
2. GROUND CHILLER DISCONNECT ENCLOSURE.
3. IDENIFY DISCONNECT.
4. MAX 25 AMP. FUSE FOR CHILLER.
5. NEED ROOFTOP SERVICE OUTLET WITHIN 25' OF CHILLER.
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH WIRING BEFORE INSPECTION, PROVIDE ACCESS TO NEW CEILING WIRING.