Permit: T06CM01455

Parcel: 13608030G

Inspection Status: Denied

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/30/2008 FIRE - FINAL Denied Not approved 5/30/08.
Bathroom addition project approved.
C of O denied.
Corrections required:
1.) Remove double-keyed locks from both front EXIT doors to Sanctuary room. Use panic hardware only.
2.) Repair all EXIT lights in Sanctuary room. All are burnt out.
3.) Emergency back-uplight in Sanctuary room is burnt out.
4.) Panic hardware on SW exit door in Sanctuary room is sticking.
5.) EXIT access doors on both sides of the stage are blocked.
6.) EXIT doors to the back area of the stage (both sides) are not readily openable
7.) Multiple cover plates are missing through out the entire complex.
8.) Need address numbers on building. at least 15" tall.
9.) Non-required portable extinguishers shall be maintained and inspected annually or removed from service.