Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/30/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECURE ELEC. DISCONNECT ON ROOF PROVIDE A GFI SERVICE RECEPTACLE ON ROOF PLANS SHOW 1 23OV CONDENSOR FOR 2 FAN COILS. 2 CONDENSORS WERE INSTALLED. PROVIDE DISCONNECTS AT FAN COILS. OVERCURRENT PROTECTION NOT SIZED CORRECTLY. |