Permit: T06CM01455

Parcel: 13608030G

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MEETING TO DISCUSS CORRECTIONS.
COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
RECALL WHEN READY
05/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED COMPLETE SET OF APPROVED DRAWINGS
2. AC UNITS NOT PER PLAN
3. OVERCURRENT PROTECTION FOR AC UNITS NOT SIZED PROPERLY
4. NEED ROOFTOP GFI SERVICE RECEPT
5. WATER HEATERS NOT PER PLAN
6. NEED DISCONNECTS FOR FAN COIL UNITS
7. NEED DISCONNECTS FOR WATER HEATERS
8. NEUTRALS #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH
9. GROUNDS #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH.
10. PANEL SCHEDULE NOT PER PLAN
11. INSTALL EXTENSIONS ON BOXES IN TILE.
MORE THAN 1/4" BACK
12. SINGLE PHASE INSTANT HOTS ON 2 POLE BREAKER
13. CANNOT REMOVE PANEL COVER PAINTED OVER
14. CANNOT FUSE NEUTRAL CONDUCTOR @ SERVICE
15. HAVE SERVICE OPEN FOR INSPECTION
16. INSTALL MAIN BONDING JUMPER
17. MARK SERVICE DISCONNECT
18. HAVE ELECTRICIAN ON SITE FOR NEXT INSPECTION