| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MEETING TO DISCUSS CORRECTIONS. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION RECALL WHEN READY |
|
| 05/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED COMPLETE SET OF APPROVED DRAWINGS 2. AC UNITS NOT PER PLAN 3. OVERCURRENT PROTECTION FOR AC UNITS NOT SIZED PROPERLY 4. NEED ROOFTOP GFI SERVICE RECEPT 5. WATER HEATERS NOT PER PLAN 6. NEED DISCONNECTS FOR FAN COIL UNITS 7. NEED DISCONNECTS FOR WATER HEATERS 8. NEUTRALS #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH 9. GROUNDS #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH. 10. PANEL SCHEDULE NOT PER PLAN 11. INSTALL EXTENSIONS ON BOXES IN TILE. MORE THAN 1/4" BACK 12. SINGLE PHASE INSTANT HOTS ON 2 POLE BREAKER 13. CANNOT REMOVE PANEL COVER PAINTED OVER 14. CANNOT FUSE NEUTRAL CONDUCTOR @ SERVICE 15. HAVE SERVICE OPEN FOR INSPECTION 16. INSTALL MAIN BONDING JUMPER 17. MARK SERVICE DISCONNECT 18. HAVE ELECTRICIAN ON SITE FOR NEXT INSPECTION |