Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/20/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/06/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/05/2006 | PLUMBING - INTERMEDIATE | Cancelled | CANCELLED BY WES | |
| 08/31/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - CORRECT TEST TEE AND P-TRAP AT LAUNDRY - FINISH UP ABOVE CEILING - OK TO COVER WALLS EXCEPT A LAUNDRY |
|
| 08/30/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PVC DWV W/TEST THROUGH ROOF IS OK - INSTALL SAFETY PLATES - WATER PIPING NOT PER PLAN; SIZING AT WH, ISOLATION VALVES AND FUTURE STUBOUT. - INSULATIONS NOT INSTALLED PER SPEC. #24 JOINTS SHALL BE NEATLY SEALED W/TAPE AND LAGGING ADHESIVE. - SECURE DROP SAR ELLS. SUPPORT OVERHEAD COPPER AT CHANGES OF DIRECTION. CU MAIN TOUCHING CONDUIT. |