Permit: T06CM01453

Parcel: 114600660

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM01453

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/23/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245
1. TIGHTEN GROUND SCREWS IN J-BOXES
2. IDENTIFY WHITE USED AS HOT AND USE TO FEED SWITCH ONLY -- NOT SWITCH LEG
3. HAVE OVERFILLED J-BOXES CHECK AND CORRECT
AS NEEDED.
4. USE WIRE NUT WITH # OF CONDUCTORS THEY ARE LISTED FOR AND ALL BARE CONDUCTOR UNDER WIRE NUT -- NOT EXPOSED.
10/19/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
RESCHEDULE INSP.