Permit: T06CM01449

Parcel: 11619360D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM01449

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/27/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/20/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/19/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/11/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
CALL RICK 1/2 HR PRIOR TO INSPECTION 591-3944

1. FINISH ROUTING LOW VOLTAGE/DATA WIRING AND USE APPROVED HANGERS, PREVIOUS CORRECTIONS OK
07/14/2006 ELECTRIC - ABOVE CEILING Partial Approval
07/12/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WORK STILL IN PROGRESS
2. REMOVE OR TAG ALL UNUSED LOW VOLTAGE WIRING.
3. REMOVE TEMPORARY LIGHTING CKTS.
4. SUPPORT ALL WIRING OFF GRID AND TO STRUCTURE.