Permit: T06CM01449

Parcel: 11619360D

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01449

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/27/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CEILING COVER ALREADY APPROVED
12/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER CEILING ELECTRICAL
12/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED J-BOXES
NEC 314.16
2. USE WIRE NUTS FOR THE MAXIMUM COMBINATION OF CONDUCTORS THEY ARE LISTED FOR ONLY - NEC 110.3 B
3. J-BOXES NOT ALLOWED TO BE MOUNTED WITH SCREWS INSIDE BOX UNLESS IN THE BACK 1/4" OF BOX - NEC 314.23 B.1
PROVIDE WIRE NUT INFORMATION FOR NUMBER OF CONDUCTORS ALLOWED.
11/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2 REPARTITIONED OFFICE AREAS -- PROVIDE RECEPTACLES AS DISCUSSED -- 3 TOTAL
09/18/2006 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
09/14/2006 ELECTRIC - INTERMEDIATE Partial Approval OK WALL COVER
05/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS ON MAIN LEVEL (HARD LIDS ALSO)