Inspection Status: Cancelled
Inspection History: FRAMING
Permit Number - T06CM01447
Inspection Description - FRAMING
Inspection Status - Cancelled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2007 | FRAMING | Cancelled | IVRS - RI canceled | |
01/18/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/16/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOUTH WALL STUCCO FOAM DEGRADED FROM SUN EXPOSURE 2) LIVING GLB REQUIRES POST PER NOTE 6 3) 3" STACK REQUIRES CLEANOUT POWDER ROOM 4) DUCTS REQUIRE 1 DUCT DIAMETER RADIUS 5) FIRESTOP W/H B-VENT ROOF AND FLOOR 6) HALL BATH SHEAR WALL DAMAGED BY PLUMBING BLOCK AND FILL 7) HALL BATH SHEAR WALL NOT CONNECTED TO TRUSS SYSTEM PER PLAN 8) ANCHOR KITCHEN WALL 9) HOLDDOWNS NOT ON SHEARWALL AT ? |
|
01/12/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) STUCCO LATH FOAM ON SOUTH SIDE OF HOUSE HAS DEGRADED FROM SUN EXPOSURE. PROVIDE LATH MANUFACTURERS ENGINEER APPROVED EVALUATION AND REPAIR 2) NO GAS TEST 3) TUB LEAK 4) SUPPORT HORIZONTAL DWV AT 4' ON CENTER 5) RED HEAD ANCHOR BOLTS LOOSE 6) STOPPED INSPECTION-TOO MANY ITEMS |