Permit: T06CM01420

Parcel: 138180600


Addresses:

6764 S 6TH AV

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/28/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/16/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWNS AT ENTRY NOT ACCPETABLE
2) EPOXY HOLDOWNS IN LOCATIONS DISCUSSED ON 6/13/06
06/15/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
REPEAT
06/13/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEAR PANEL STILL REQUIRED
2) NEW TRUSS CALC'S MUST HAVE CITY STAMP
3) GABLE END BRACES MUST BE ATTACHED TO TOP OF WALL
06/06/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEAR PLAN FOR "NO GARAGE OPTION" MUST BE USED: RETRO H.D. FOR SHEAR PANEL #2, DOOR PLACEMENT NOT PER PLAN AND WINDOW MISSING ON EAST WALL
2) STRAP TOP PLATE HORIZONTALLY WHERE BEAM AT PATIO INTERUPS CONTINUITY
3) REMOVE CLIPS AND PROVIDE RELIEF FOR TRUSSES NOT INTENDED TO BEAR ON ENTRY WALL
4) A35'S AT BIRD BLOCKS MUST HAVE SUFFICIENT NAILING TO TOP PLATE
5) RAT RUNS PER TRUSS CALC'S
6) ENTRY TRUSSES DON'T MATCH CALCS
7) STOPPED INSPECTION