Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM01414
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* COORDINATE WITH WHOEVER FOR ROOF ACCESS FOR FINAL. |
|
06/12/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CONFERENCE RM. SOUTH WALL - 5FT 10"X12" DUCT TERMINATION FROM ADJOINING SPACE. WHAT IS IT? CONDITIONED AIR - RAW, NO INSULATION. 2. SPOT INSUL. WHERE NECESSARY 3. PICK UP FLEX OFF OF GRID, LONG RADIUS 90 DEGREES. 4. INSULATE ALL SUPPLY/RETURN DUCT, PATCHES, ETC. ABOVE GRID. 5. BLUE LINE MACHINE VENT. IS DOOR REMAINING OR GOING. CAN'T DUMP EXHAUST WITHIN 10 FT. OFF DOORS, WINDOWS, ETC. |