Permit: T06CM01414


Addresses:

7150 S TUCSON BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/15/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
COORDINATE WITH WHOEVER FOR ROOF ACCESS FOR FINAL.
06/12/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CONFERENCE RM. SOUTH WALL - 5FT 10"X12"
DUCT TERMINATION FROM ADJOINING SPACE. WHAT IS IT? CONDITIONED AIR - RAW, NO INSULATION.
2. SPOT INSUL. WHERE NECESSARY
3. PICK UP FLEX OFF OF GRID, LONG RADIUS 90 DEGREES.
4. INSULATE ALL SUPPLY/RETURN DUCT, PATCHES, ETC. ABOVE GRID.
5. BLUE LINE MACHINE VENT. IS DOOR REMAINING OR GOING. CAN'T DUMP EXHAUST WITHIN 10 FT. OFF DOORS, WINDOWS, ETC.