Permit: T06CM01403

Parcel: 134162990

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/12/2006 BUILDING - FINAL Approved IVRS - Inspection :*
12/12/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH UP HALL BATH
12/11/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
12/06/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SET SCREW MISSING IN VACUUM BREAKER @ REAR HOSE BIB
2. SPARK ARRESTER NEEDED ON WATER HTR. FLUE
3. 1" CLEARANCE REQ'D @ WATER HTR B-VENT 6" CLEARANCE REQ'D @ SINGLE WALL
4. COVER MISSING ON EXHAUST DUCT OVER DRIVEWAY
5. INSTALL EXTERIOR LIGHTS
6. STOPPED INSPECTION
12/04/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*