Permit: T06CM01397

Parcel: 13708021C


Addresses:

5601 S 12TH AV #09


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01397

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
CHECKED ONLY ON NOTICE DSC GAVE 5/8/06
ALL ELSE COVERED.
05/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & CEILINGS EXCEPT AIR HANDLER - MUST USE CONDUIT OR FLEX METAL - NO ROMEX.
04/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
USE APPROVED BOX & FITTINGS FOR MC CABLE - PLASTIC BOX LISTED FOR ROMEX ONLY.
04/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) THESE UNITS WHERE NOT DAMAGED BY FIRE TFD HAD TEP DISCONNECT ALL METERS TO THIS BLDG
04/05/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTES:
BOND BUSHINGS OR BONDING LOCKNUTS REQUIRED AHEAD OF OVERCURRENT DEVICES AT SERVICE.