Permit: T06CM01380

Parcel: 122173860

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY/EXIT LIGHTING IS NOT PER PLAN OR CODE
NEC 700.12 (E)
2. INSTALL BOX EXTENDERS AS REQUIRED BY NEC 314.20

NOTE: WILL NEED TO PAY REINSPECTION FEE BEFORE FINAL APPROVAL IF NEXT TRIP NOT CORRECT.
08/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ELECTRICIAN ON SITE TO HELP WITH INSPECTION (WITH PLANS) LEAVE HIS NAME AND NUMBER WHEN FINAL IS CALLED AND I WILL GIVE HIM A CALL 1/2 HR PRIOR.
07/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CORRECTIONS HAVE NOT BEEN MADE
07/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY
1. CORRECTLY IDENTIFY PANEL DIRECTORY'S - NEC 408.4
2. EMERGENCY LIGHTING TO COMPLY WITH NEC 700.12(E)
3. USE BOX EXTENDERS AS REQUIRED BY NEC 314.20
4. HAVE ENCLOSURES OPEN FOR INSPECTION
5. CAN'T FINE NEW LOADS ON PLAN FOR PANEL CALCS?

VALASKO ELECTRIC
744-1195
07/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE PLANS ON SITE
2. PROVIDE ATTIC ACCESS
3. HAVE CONTRACTOR ON SITE WITH PRIOR ELECTRICAL INSPECTION REPORTS.