Permit: T06CM01380

Parcel: 122173860

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/23/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/04/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. COMPLETE CORRECTIONS FROM PREVIOUS INSPECTION.
04/03/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO INSTALL NAIL PLATES AS NEEDED NEC 300.4
2. UNCOVER ELECTRICAL IN WALLS FOR INSPECTION.
3. INSTALL OUTLETS AND LIGHTING PER PLAN
4. HAVE OVERFILLED BOXES NEC 314.16
5. SUPPORT AND SECURE MC CABLE NEC 320.23, NEC 330.23, NEC 330.30
6. MC TERMINATIONS TO BE ALL THE WAY IN CONNECTOR NEC 110.3 ETC
7. ALL J-BOXES WILL REQUIRE PROPER GROUNDING AND COVERS.