Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* WATER TEST WATER PIPING & WASTE & VENT THRU ROOF OK |
|
| 10/09/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WASTE & VENT PIPING TO BE TESTED THRU ROOF. 2. ABS & PVC CANNOT BE INTERMINGLED WITHOUT CORRECT APPROVED TRANSITION COUPLING. PROVIDE LIKE FOR LIKE MATERIALS FOR WASTE & OVERFLOW FOR TUBS. 3. PROVIDE WATER DISTRIBUTION PER PLAN. 4. LAVS TO HAVE LONG RADIUS DRAINAGE FITTINGS FOR STUB OUT OF WALL AND DRAIN ARM MAY ONLY HAVE 135 DEG. CHANGE OF DIRECTION. 5. PROVIDE MINIMUM 18" WEIR OF TRAP TO WASHER BOX INLET AND USE FACTORY MADE P-TRAP. |